8 min readFor facility managers3 illustrations

What a hazardous location is

A hazardous location is any area where flammable gas, vapour, combustible dust or fibres could be present in enough quantity to ignite. In those areas, an ordinary light switch, motor or receptacle can be an ignition source.

Across Alberta and BC this is not just an oil and gas issue. Common examples include:

  • Paint and spray booths, and solvent mixing rooms
  • Fuel dispensing and vehicle repair pits
  • Battery charging rooms where hydrogen can collect
  • Grain handling, woodworking and other dusty processes
  • Wastewater wet wells and lift stations
  • Gas plants, well sites, compressor stations and tank farms

Electrical work in these areas is governed by the hazardous locations rules of the Canadian Electrical Code, along with the relevant CSA standards for equipment. The rules are detailed, and the details matter.

Zones, Divisions and area classification

Classification describes what could be present and how often. Canada uses a Zone system for new work with flammable gases and vapours, and you will still see the older Class and Division system on existing facilities and equipment.

Zone (gas)Rough Division equivalentMeaning
Zone 0Division 1Flammable atmosphere present continuously or for long periods
Zone 1Division 1Likely to be present in normal operation
Zone 2Division 2Not likely in normal operation, and only briefly if it happens

Dusts have their own Zones (20, 21 and 22) or Class II, and fibres are handled separately. The table is a simplification: the systems do not map perfectly, so always work from your site's documents.

FIG 01Alberta Electrical
Plan view of a shop with a spray booth shaded as Zone 1 inside, a Zone 2 envelope around it, and an electrical panel located outside the classified area. EXAMPLE: SPRAY BOOTH IN A SHOP (PLAN VIEW) GENERAL SHOP AREA: UNCLASSIFIED ZONE 2 / DIV 2: GAS ONLY IF SOMETHING GOES WRONG BOOTH INTERIOR ZONE 1 / DIV 1 GAS IN NORMAL USE PANEL KEEP ORDINARY GEAR OUTSIDE MIX RM EXTENTS COME FROM THE AREA CLASSIFICATION DRAWING, NOT FROM THIS SKETCH
A simplified plan of a spray booth showing the higher-risk area inside the booth, a lower-risk envelope around it, and ordinary equipment kept outside.

The extent of each area is set on an area classification drawing, prepared by someone qualified to do it, usually an engineer, based on the substances, ventilation and release sources. If your facility does not have one, or the process has changed since it was drawn, that is the first thing to fix.

How equipment is protected

Equipment in a classified area must be certified and marked for that area. There are several protection methods, often abbreviated with Ex codes:

FIG 02Alberta Electrical
Three panels showing an explosionproof enclosure with a conduit seal, an intrinsic safety barrier between safe and hazardous areas, and a purged panel fed with clean air. THREE COMMON PROTECTION METHODS SPARK SEAL CONTAIN IT EXPLOSIONPROOF (FLAMEPROOF, Ex d) SAFE AREAHAZ AREA BARRIER TX INTRINSIC SAFETY (Ex i): TOO LITTLE ENERGY TO IGNITE PANEL CLEAN AIR IN KEEP GAS OUT PURGED / PRESSURIZED (Ex p)
Three common protection methods: contain an internal explosion, limit energy so ignition cannot happen, or keep flammable gas out of the enclosure with clean air.
  • Explosionproof or flameproof (Ex d): a heavy enclosure that contains an internal ignition and cools escaping gases. Conduit seals stop gas and flame travelling through the conduit.
  • Intrinsic safety (Ex i): limits the energy in a circuit so it cannot ignite the atmosphere, typically using barriers or isolators in the safe area. Common for instruments.
  • Increased safety (Ex e): prevents sparks and hot spots through construction, used for terminal boxes and some motors.
  • Purged or pressurized (Ex p): keeps flammable gas out of an enclosure with clean air or inert gas, with monitoring if pressure is lost.
  • Non-incendive and similar methods: suited to Zone 2 or Division 2 areas only.

Reading a nameplate

Certified equipment carries markings that tell you where it can be used. It must suit the area's classification, the gas or dust group, and the temperature class, which limits how hot the surface can get compared with the ignition temperature of the substance.

FIG 03Alberta Electrical
Example nameplate reading Ex d IIB T4 Gb and Class I Div 1 Groups C D T4, with leader lines labelling method, gas group, temperature class and protection level. READING AN EQUIPMENT NAMEPLATE (EXAMPLE) METHOD GAS GROUP TEMP CLASS PROTECTION LEVEL Ex d IIB T4 Gb ZONE STYLE MARKING Class I, Div 1, Groups C, D T4 CLASS/DIV STYLE PLUS A CERTIFICATION MARK FROM AN ACCEPTED BODY
How to read a hazardous location nameplate: the marking tells you the protection method, gas group, surface temperature class and the area it suits.
SafetySmall changes break certification

A missing bolt on a flameproof cover, an extra hole drilled in an enclosure, the wrong cable gland or a seal that was never poured can each defeat the protection. Any modification or repair in a classified area should be done only by qualified electricians or instrument technicians.

What owners are responsible for

  • Keep a current area classification drawing and update it when the process, building or ventilation changes.
  • Buy only equipment certified and marked for the area. A consumer-grade fan or work light in a booth is a real hazard.
  • Keep records of installed equipment and its certification.
  • Arrange periodic inspection of enclosures, seals, glands and grounding, and fix findings promptly.
  • Control hot work and portable equipment with a permit system.
  • Make sure contractors working in the area know the classification before they start.

When you renovate, check the classification early. Moving a booth, changing ventilation or adding a battery room can change where classified areas are, which changes what electrical equipment you need. Permits apply as for any electrical work in Alberta, or through Technical Safety BC or the local authority in BC.

How we can help

We install and maintain electrical and instrument equipment in classified areas, including gas detection and field instrumentation, and can work from your engineer's classification drawing on plant retrofits. For the gas side of the picture, see gas detection in shops and plants.

Common questions

Who decides if an area is classified?

Area classification is normally done by a qualified person, typically an engineer, using recognized practices for the substances and ventilation involved. The electrical contractor installs to that drawing; it does not set the classification itself.

Is a residential garage a hazardous location?

Typical home garages are generally not treated as classified locations, but commercial repair garages, fuel dispensing and pits can be. Check with the permit authority or an engineer for your specific use.

Can we use Division-rated equipment in a Zone area?

In many cases there are allowances, but it depends on the specific classification and the equipment markings. Have the installation reviewed rather than assuming.

Does ventilation make an area unclassified?

Ventilation can reduce the extent or level of classification, but only when it is designed, monitored and documented as part of the classification. Turning on a fan is not enough.

About this guideGeneral information, not a site assessment

Codes and permit rules change and every building is different. For work on your system, talk to a licensed electrician and your local permit authority.

Keep reading

More on instrumentation, controls and automation

All 12 guides →

Need an electrician?

Call the 24/7 line or send a request and we'll set up a consultation and a free estimate.

Call 24/7Request service