Where gas detection shows up
Fixed gas detection protects people and property in places where a leak or buildup could go unnoticed. In Alberta and BC it is common in:
- Vehicle repair shops and fleet garages (carbon monoxide, nitrogen dioxide from diesel, combustibles)
- Underground parkades, where CO and NO2 detection often controls the exhaust fans
- Boiler and mechanical rooms (combustibles, CO, refrigerant)
- Battery rooms (hydrogen)
- Oil and gas facilities, wastewater plants and lift stations (H2S, methane, oxygen deficiency)
- Food and cold storage with ammonia or CO2 systems
Requirements come from several places: building and mechanical codes, the Alberta OHS Code or WorkSafeBC rules for worker exposure, fire codes, and sometimes your insurer or a permit condition. Which ones apply depends on the building and the process.
Matching the sensor to the gas
| Sensor type | Typical use | Things to know |
|---|---|---|
| Catalytic bead | Combustible gases as percent of lower explosive limit (LEL) | Needs oxygen to work; some chemicals can poison it |
| Infrared | Hydrocarbons, CO2 | Resists poisoning; cannot see hydrogen |
| Electrochemical | Toxic gases such as CO, H2S, NO2, and oxygen level | Limited sensor life; affected by extreme cold and dryness |
| Semiconductor and others | Refrigerants and specialty gases | Check cross-sensitivity to other gases |
Choosing the wrong technology is a common and serious mistake. A catalytic sensor in an oxygen-poor space will under-read, and an infrared sensor will never alarm on hydrogen. The gas list and the environment should drive the choice.
Where the sensors go
Placement depends on gas density, likely leak points, airflow and temperature. Lighter gases tend to collect near the ceiling, heavier ones near the floor and in pits and trenches. Toxic gases that mix with air are usually monitored in the breathing zone where people work.
Sensors also need to be reachable for testing. A detector mounted where nobody can get a ladder or a gas cylinder to it tends not to get maintained.
What the system does when it alarms
Most systems use at least two alarm levels. The low level warns people and increases ventilation; the high level calls for evacuation and may shut off fuel or process equipment. Setpoints should be based on the exposure limits and safety requirements that apply to your workplace, which is why we do not quote numbers here.
Just as important is the fault signal. A sensor that has failed or been disconnected should never look the same as clean air. Make sure faults show up somewhere a person will act on them, whether that is a local panel, the building automation system or a remote alert.
Treat every gas alarm as real until the area has been checked by someone trained to do it. Do not silence or bypass a detector to keep working.
Keeping it trustworthy
- Bump tests prove each sensor responds and alarms. Follow the manufacturer's frequency and any workplace requirement.
- Calibration against certified test gas, by trained technicians, at the required interval.
- Sensor replacement before end of life. Electrochemical cells in particular wear out.
- Records for every test, calibration and alarm event.
- Functional tests of outputs: does the fan actually start, does the valve actually close?
Gas detection is a life-safety system, so it deserves a place at the top of your calibration schedule. In a classified area, the detectors and wiring must also meet hazardous location requirements.
Problems we commonly find
- Sensors past their service life, still installed and still showing a steady clean-air reading
- Detectors relocated during a renovation to a spot that no longer suits the gas
- Alarm outputs disconnected after a nuisance alarm and never reconnected
- Fault signals that go nowhere, so a dead sensor goes unnoticed for months
- Outdoor or unheated sensors struggling in a -30 C cold snap because the enclosure or sensor is not rated for it
- No records, so nobody can say when the last calibration happened
Each of these is easy to fix once it is found. The value of a periodic inspection by someone who knows the system is that it finds them before an emergency does.
Planning a new or upgraded system
Start with a gas hazard review: what gases, where they come from, who could be exposed, and which codes and rules apply. From there a design sets sensor types, locations, alarm levels and outputs. Our gas detection service covers installation, wiring, commissioning and ongoing testing by instrument technicians and electricians, and we can tie alarms into your HVAC controls for ventilation.
Common questions
Is a portable monitor enough instead of a fixed system?
Portable monitors protect the person wearing them and are essential for confined space entry. Fixed systems protect an area continuously and can trigger ventilation and shutdowns. Many sites need both.
How long do gas sensors last?
It depends on the sensor type, the gas, the environment and exposure history. Manufacturers publish expected lives; your test records will show when sensors start to weaken.
Why does our parkade CO system run the fans all the time?
Common causes are a failed or drifting sensor reporting a fault, a controller set to run on fault, or setpoints that do not match the design. A calibration and functional test usually finds it.
Can gas detection connect to our building automation system?
Yes. Alarms, faults and gas levels can be sent to a BAS or remote monitoring system, though the gas detection controller should still operate its own safety outputs directly.
Codes and permit rules change and every building is different. For work on your system, talk to a licensed electrician and your local permit authority.