Why calibration drifts out of sight
Every measuring instrument drifts. Pressure transmitters shift with temperature cycling and vibration, gas sensors lose sensitivity as they age, flow meters wear, and temperature sensors can open up or degrade. Most of the time the reading still looks believable, which is exactly the problem.
A calibration program catches drift before it causes a bad batch, a missed alarm, a wasted energy bill or an incident. The hard part is not the calibration itself. It is deciding which instruments, how often, and to what standard, then sticking to it.
In Alberta, Instrument Technician is a designated trade of its own. Calibration and adjustment of process instruments is normally done by instrument technicians, with electricians handling power and wiring.
Start with an instrument list
You cannot schedule what you have not listed. Build or clean up an index with, at minimum:
- Tag number and location
- What it measures and its calibrated range
- What it does: indicate, control, alarm, shut down, or report to a regulator or customer
- Make, model and serial number
- Required accuracy (tolerance) for its job
- Last calibration date and result
Many sites find instruments during this step that nobody knew existed, or that have been disconnected for years. It is worth walking the site with the drawings in hand.
Rank by criticality
Not every gauge deserves the same attention. A common method sorts instruments into tiers based on the consequence of a wrong reading.
| Tier | Typical examples | Approach |
|---|---|---|
| 1: critical | Safety shutdowns, gas detection, custody transfer or regulatory reporting, product quality | Shortest interval, documented procedure, strict tolerance, verify after any repair |
| 2: important | Control loops that affect efficiency or equipment life, energy metering | Regular interval, adjust based on as-found history |
| 3: indication | Local gauges, non-critical trend points | Longer interval, check opportunistically or replace on failure |
We deliberately do not give fixed months here. The right interval depends on the device, the manufacturer's recommendation, any regulation or permit condition that applies, and your own drift data. For gas detectors in particular, follow the manufacturer's bump test and calibration requirements and any rules that apply to your workplace.
Where an instrument is used for safety, environmental reporting or billing, the interval and method may be set by a regulator, permit, contract or standard. Confirm those requirements before you set your own schedule.
What a good calibration record shows
A record should let someone else repeat the work and trust the result. Look for:
- As-found readings at several points (often 0, 25, 50, 75 and 100 percent) before anything is touched
- As-left readings after adjustment
- The tolerance it was checked against and a pass or fail
- The reference equipment used, with its own calibration certificate traceable to national standards
- Date, technician and any notes on condition, damage or repairs
The as-found data is the valuable part. It tells you whether the instrument was out of tolerance while it was in service, which may mean product, reports or alarms during that period need a second look.
Adjust the interval using your own data
After a few cycles, your records start telling you what the schedule should be:
- Always within tolerance as found, with little drift? You may be able to stretch the interval, if no rule prevents it.
- Frequently out of tolerance as found? Shorten the interval, and ask why. The device may be wrong for the service, poorly installed, or failing.
- Drifts every winter? Look at enclosure heating, heat tracing on impulse lines, and installation location.
Use a computerized maintenance system or even a well-kept spreadsheet so due dates do not depend on one person's memory.
Review the whole program once a year. Instruments get added, removed or change duty, and a tier 3 indicator that someone now uses to make operating decisions may deserve a promotion. Retired instruments should come off the list so crews are not chasing devices that no longer exist.
Making it manageable
Group calibrations by area or by shutdown window to reduce travel and process interruptions. Keep a small stock of spares for tier 1 devices so a failed unit can be swapped and calibrated on the bench. Tie in the loop check whenever an instrument is replaced, so the controller scaling is verified along with the device.
Our instrument calibration service can build the instrument index, set up tiers and carry out the field work, and our industrial maintenance crews can coordinate it with your electrical shutdowns.
Common questions
Is calibrating the same as a bump test on a gas detector?
No. A bump test briefly exposes the sensor to gas to prove it responds and alarms. A calibration adjusts the reading against a known gas concentration. Both are normally required, at frequencies set by the manufacturer and your workplace requirements.
Can we calibrate in place or does it have to go to a shop?
Many instruments can be calibrated in the field with portable reference equipment. Some, like certain flow meters or analyzers, are better checked on a bench or by the manufacturer. Your procedure should say which.
What does traceable mean?
It means the reference equipment used was itself calibrated against higher-level standards in an unbroken chain back to national measurement standards, with certificates to prove it.
Do we need to recalibrate after a repair?
Yes, for anything where accuracy matters. Any repair, sensor swap or re-ranging should be followed by a calibration check and, ideally, a loop check to the controller.