4-20 mA loops explained for owners and operators

What a 4-20 mA signal is, why industry still relies on it, how to read one, and what usually goes wrong with analog instrument loops.

7 min readFor facility managers3 illustrations

Why a current signal, and why 4 to 20

Walk through almost any plant, lift station or mechanical room in Alberta and you will find instruments talking to a controller over a pair of wires carrying a small DC current between 4 and 20 milliamps. It is old technology, and it is still everywhere because it works.

A 4-20 mA loop sends a measurement, like pressure, level, flow or temperature, as a current instead of a voltage. Current is the same at every point in a series circuit, so long cable runs, terminal blocks and a bit of wire resistance do not change the reading the way they would with a voltage signal. It also shrugs off a lot of electrical noise from nearby motors and drives.

The range starts at 4 mA, not zero. That live zero means the controller can tell the difference between "the tank is empty" (4 mA) and "the wire is cut" (0 mA). Anything well below 4 mA is a fault, not a reading.

FIG 01Alberta Electrical
Graph showing a straight line from 4 mA at zero percent to 20 mA at full scale, with 12 mA at midpoint and a fault zone below 4 mA. 0 mA 4 mA 20 mA 12 mA = 50% 0% OF RANGE 100% 0 TO 4 mA: FAULT / DEAD ZONE ABOVE 20 mA: OVER-RANGE LIVE ZERO: 4 mA MEANS "BOTTOM OF RANGE", NOT "DEAD"
How 4 to 20 mA maps to 0 to 100 percent of a transmitter's range, with the dead zone below 4 mA used to flag a broken wire or failed device.

How the loop is wired

Most field transmitters are two-wire, loop-powered devices. One pair of conductors carries both the power the transmitter needs and the signal it sends back. A DC supply (very often 24 V) pushes current around the loop, the transmitter regulates how much flows, and the controller's input card measures it, usually by reading the voltage across a precision resistor.

FIG 02Alberta Electrical
Diagram of a 24 VDC supply, a pressure transmitter and a PLC analog input with a 250 ohm resistor wired in one series loop. TRANSMITTER PT FIELD DEVICE 24 VDC LOOP SUPPLY PLC ANALOG INPUT CARD 250R CURRENT FLOWS ONE WAY SAME CURRENT EVERYWHERE IN THE LOOP READS 1 TO 5 V TWO WIRES CARRY POWER AND SIGNAL + -
A two-wire 4-20 mA loop: the supply, field transmitter and PLC input resistor sit in one series circuit, so the same current flows through every part.

You will also meet four-wire instruments, which have separate power (often line voltage) and a separate signal pair. Analyzers, some flow meters and devices with heaters or big displays are usually four-wire. The distinction matters when you are troubleshooting or adding devices, because the loop supply and wiring are different.

  • Loop supply: the DC source, sometimes on the I/O card, sometimes a separate power supply in the panel.
  • Transmitter: converts the process measurement into a current.
  • Receiver: the PLC, BAS controller, recorder or indicator that reads the current.
  • Wiring path: field cable, junction boxes, marshalling terminals, fuses and any barriers or isolators in between.

Reading the number

Converting a current to an engineering value is simple proportion. The 16 mA span between 4 and 20 maps to the instrument's calibrated range. If a pressure transmitter is ranged 0 to 1,000 kPa:

Loop currentPercent of rangeReading
4 mA0%0 kPa
8 mA25%250 kPa
12 mA50%500 kPa
16 mA75%750 kPa
20 mA100%1,000 kPa

The math only works if the transmitter's range and the controller's scaling match. A surprisingly common problem after a device swap is a new transmitter ranged 0 to 1,600 kPa feeding a controller still scaled for 0 to 1,000. The loop looks healthy and the number is simply wrong.

TipWrite the range on the tag

Keep the calibrated range on the instrument tag, the loop drawing and the controller configuration. When all three agree, a replacement is a quick job instead of a puzzle.

Smart transmitters and HART

Many modern transmitters are "smart". Besides the analog current, they can carry a small digital signal on the same wires using the HART protocol. The analog value still drives the control system, while the digital layer lets a technician read the tag, range, sensor health and diagnostics with a handheld communicator or a HART-capable input card.

FIG 03Alberta Electrical
Drawing of a flat DC line at 12 mA with a small sine wave riding on it, labelled analog value and HART digital data. DC LEVEL = PROCESS VALUE (12 mA) SMALL DIGITAL SIGNAL RIDES ON TOP (HART) ANALOG CARRIES: THE ONE MAIN MEASUREMENT DIGITAL CAN CARRY: TAG, RANGE, DIAGNOSTICS ONE PAIR OF WIRES, TWO LAYERS A HANDHELD COMMUNICATOR OR A HART-CAPABLE INPUT CARD CAN READ THE DIGITAL LAYER WITHOUT DISTURBING THE 4-20 mA VALUE.
A HART-capable transmitter overlays a small digital signal on the steady 4-20 mA current, adding configuration and diagnostic data on the same wires.

Smart devices also let you re-range in software, which is convenient and a little dangerous. Changing the range in the transmitter without changing the scaling at the controller gives you the mismatch described above. Changes should go through whoever owns your instrument records.

What usually goes wrong

Most 4-20 mA problems are wiring and documentation problems, not mysterious electronics:

  • Loose or corroded terminals in junction boxes, especially outdoors where frost and condensation cycle through an Alberta winter.
  • Shield grounded at both ends, creating a ground loop that shows up as a noisy or drifting reading.
  • Not enough loop voltage after someone adds an indicator or barrier, so the transmitter cannot drive the full 20 mA.
  • Scaling mismatch between the transmitter range and the controller.
  • Water in conduit or cable glands, which can short or leak current and shift readings.
  • Sensor problems such as plugged impulse lines on pressure and level transmitters.

A reading stuck at exactly 4 mA, below 4 mA, or pinned above 20 mA is a strong hint the device is reporting a fault rather than a real process value. Many transmitters drive their output to a defined fault level on purpose so the controller can alarm on it.

SafetyLeave live testing to the trades

Measuring loop current means opening junction boxes and panels, and in hazardous areas it needs specific procedures and test equipment. Diagnosis should be done by instrument technicians or electricians, not by operators with a borrowed meter.

When to call for help

Ask for help when a reading does not match what you can see in the process, when a loop alarms intermittently, or when you are adding or replacing instruments. A good service visit checks the device, the wiring and the controller scaling together, then updates the records. See what a loop check is and instrument calibration schedules for the next steps, or our field instrumentation service.

Common questions

Is 4-20 mA being replaced by digital networks?

Digital fieldbus and Ethernet-based instruments are growing, but 4-20 mA remains the most common analog signal in existing plants and buildings. Most sites run a mix, and new devices often support both.

Can I add a local display to an existing loop?

Usually yes, with a loop-powered indicator wired in series. It uses some of the available loop voltage, so someone should confirm the supply can still drive the transmitter to full scale, especially on long cable runs.

Why does my reading go to zero in a cold snap?

Common causes are moisture in a junction box or gland freezing and shifting, a heat-traced impulse line that has frozen, or a power supply problem. Have a technician check the wiring, enclosure heating and any heat tracing.

Do building automation systems use 4-20 mA too?

Yes. Many BAS controllers accept 4-20 mA and 0-10 V inputs for things like duct static pressure, CO2 and flow, alongside resistive temperature sensors.

About this guideGeneral information, not a site assessment

Codes and permit rules change and every building is different. For work on your system, talk to a licensed electrician and your local permit authority.

Keep reading

More on instrumentation, controls and automation

All 12 guides →
Instrumentation, controls and automation · 7 min

How to set instrument calibration schedules

A practical approach to deciding how often each instrument gets calibrated, what a good calibration record contains, and how to adjust intervals using your own data.

Read the guide →
Instrumentation, controls and automation · 6 min

What a loop check is and why it matters

A loop check proves that each instrument and control signal is wired, configured and displayed correctly from the field device to the operator screen. Here is what it involves and when you need one.

Read the guide →
Instrumentation, controls and automation · 8 min

Hazardous locations basics for shops and plants

What makes an area a hazardous location, how Zones and Divisions work, the common ways electrical equipment is protected, and what owners are responsible for.

Read the guide →

Need an electrician?

Call the 24/7 line or send a request and we'll set up a consultation and a free estimate.

Call 24/7Request service