Instrumentation, controls and automation

SCADA and remote monitoring for remote sites

How SCADA ties lift stations, reservoirs, pump houses and well sites together, the communication options for rural Alberta and BC, and what makes a remote system reliable.

7 min readFor facility managers2 illustrations

What SCADA does

SCADA stands for supervisory control and data acquisition. In plain terms, it lets a small team watch and run equipment spread across many sites from one place. Each site has a controller, usually a PLC or remote terminal unit (RTU), that runs the local equipment. SCADA collects data from all of them, stores the history, shows it on screens and sends alarms to whoever is on call.

Municipal water and wastewater systems, irrigation districts, oil and gas operators, agricultural operations and owners of multiple buildings all use some form of SCADA or remote monitoring.

FIG 01Alberta Electrical
Three remote sites with controllers and communication links feeding a central SCADA server, which feeds an operator screen, phone alerts and reports. REMOTE SITES REPORTING TO ONE CONTROL ROOM LIFT STATIONPLC + CELL MODEM RESERVOIRRTU + RADIO WELL OR PADRTU + SATELLITE SECURE LINKS SCADA SERVER HISTORIAN ALARMS OPERATOR HMI ON-CALLPHONE ALERT REPORTS
A typical SCADA layout: controllers at each remote site send data over cellular, radio or satellite to a central server that stores history and pushes alarms to on-call staff.

Choosing how sites communicate

In rural Alberta and BC, communications are often the hardest part of the design. Common options:

LinkStrengthsWatch for
CellularEasy to deploy where coverage is good; good bandwidthCoverage gaps, carrier network changes, data plans
Licensed or unlicensed radioOwner-controlled, no monthly carrier feeNeeds line of sight or repeaters; path study required
SatelliteWorks almost anywhereLatency, cost per data and weather effects
Fibre or wiredFast and reliableOnly practical where it already exists or is close

Many systems use a primary and a backup link for critical sites. Ask for a coverage or radio path survey before choosing, rather than assuming a phone shows enough bars.

Protocols you may hear about include Modbus, DNP3 and MQTT. DNP3 and similar protocols support time-stamped data and report-by-exception, which helps when bandwidth is limited and you need to know exactly when something happened.

Designing for remote and cold

A remote site may be hours away and visited weekly or less, so the hardware has to look after itself.

FIG 02Alberta Electrical
Enclosure layout with a PLC, modem, power supply, battery, heater and terminals, plus an antenna and a solar panel outside. REMOTE SITE ENCLOSURE BUILT FOR WINTER PLC / RTU+ I/O CELL / RADIOMODEM 24 VDC + UPS BATTERY HEATER +THERMOSTAT TERMINALS ANTENNA SOLAR PANELWHERE NO GRID DOOR SWITCH,ENCLOSURE TEMPAND POWER ALARMS SIZE BATTERY AND HEAT FOR -40 C AND SHORT DAYS
A remote site enclosure designed for Alberta and northern BC winters, with heating, battery backup, communications and alarms on the enclosure itself.
  • Power: battery backup sized to keep communications and key alarms alive through an outage; solar where there is no grid.
  • Heat: enclosure heaters and insulation so electronics, batteries and displays stay within their rated range.
  • Self-monitoring: alarms for power failure, low battery, high or low enclosure temperature, intrusion and communication loss.
  • Local control: the site should keep running safely if communications fail, not wait for instructions.
  • Surge and lightning protection on power, antenna and field wiring.

Alarms that people trust

A SCADA system lives or dies on its alarms. Too many nuisance alarms and on-call staff start ignoring them; too few and something important is missed.

  • Give each alarm a clear priority and a response.
  • Use delays and deadbands to stop chattering alarms.
  • Route alarms to the right person, with escalation if nobody acknowledges.
  • Review alarm history regularly and fix the worst offenders.
TipTest the call-out

Schedule a test alarm each month to prove that phones, texts or calls actually reach the on-call person. Carrier and contact list changes break call-outs quietly.

History, reports and compliance

The historian is the quiet workhorse of a SCADA system. It stores every value and alarm with a time stamp, which turns into:

  • Daily and monthly reports for flows, levels, run hours and energy use
  • Evidence for regulators where reporting is required, for example on some water and wastewater systems
  • Maintenance insight, such as pumps whose run time is creeping up as they wear
  • Answers after an incident: what happened, in what order, and when

Make sure the historian is backed up and that time stamps come from the remote sites where possible, not just from when the server received the data. When a link drops and catches up later, that difference matters. If you have reporting obligations, confirm with your regulator what records you must keep and for how long, then set retention to match.

Security for remote access

Remote access is the point of SCADA and also its biggest risk. Avoid exposing controllers directly to the internet, use encrypted connections, give each person their own login, and keep track of who has access. Our guide on cybersecurity for building and plant controls covers the basics.

SafetyRemote control needs local safety

Starting pumps or opening valves remotely must never bypass local safety interlocks. People working at a site need lockout procedures that remote operators cannot override.

Getting started

Start small if you need to: monitoring a few critical alarms by cellular is far better than a weekly drive-by. A well-designed system can grow into full SCADA later. Our SCADA and remote monitoring team designs, builds and services remote systems, including the PLC systems and UPS systems at each site.

Common questions

What is the difference between a PLC and an RTU?

Both are controllers at a site. RTUs are designed around remote communication, low power and data logging; PLCs are designed around local control. Modern products overlap heavily.

Can we add monitoring to an old lift station without replacing everything?

Often yes. A small controller or cellular gateway can read existing alarms and signals and report them, leaving local controls in place until a larger upgrade.

What happens if the cellular network goes down?

A well-designed site keeps running under local control, logs data, and reports communication loss as an alarm. A backup link can be added for critical sites.

Who owns the data?

You should. Make sure contracts give you access to the historian data and the configuration, regardless of who hosts the server.

About this guideGeneral information, not a site assessment

Codes and permit rules change and every building is different. For work on your system, talk to a licensed electrician and your local permit authority.

Keep reading

More on instrumentation, controls and automation

All 12 guides →
Instrumentation, controls and automation · 7 min

What a building automation system does

A plain-language look at building automation: what it controls, how it is put together, and how owners and operators use it to save energy and catch problems early.

Read the guide →
Instrumentation, controls and automation · 7 min

Building automation for small and mid-size buildings

Practical building automation options for offices, retail, clinics, churches, schools and light industrial buildings, and how to choose one you can live with for years.

Read the guide →
Instrumentation, controls and automation · 7 min

Sub-metering and energy dashboards that actually get used

How electrical sub-metering works, where meters pay off, what to show on an energy dashboard, and the rules to know before you bill tenants.

Read the guide →

Need an electrician?

Call the 24/7 line or send a request and we'll set up a consultation and a free estimate.

Call 24/7Request service